A Guide to Troubleshooting and Maintenance of Ten Common Issues with Electromagnetic Flowmeters

A Guide to Troubleshooting and Maintenance of Ten Common Issues with Electromagnetic Flowmeters


    As a key instrument in modern industrial process control, electromagnetic flowmeters are widely used in water treatment, chemical, food and other industries due to their high precision and low pressure loss. However, in actual operation, problems such as inaccurate measurement and abnormal signals occur from time to time. Mastering the following ten common troubleshooting and maintenance techniques can effectively ensure the stable operation of production.

Problem 1: No flow signal output

  Check if the power is connected and the wiring is secure. Confirm that the converter parameters are set correctly, especially the range and instrument coefficient. Measure the resistance between the electrodes and the ground to determine if the electrodes are covered or damaged by insulating substances.

Problem 2: Large fluctuations in flow display

   First, check if the pipeline is fully filled with fluid and if there are bubbles or slurry noise. Check if the grounding is good and ensure that the grounding ring or grounding electrode is reliably connected. Stay away from strong interference sources such as frequency converters and high-power motors.

Problem 3: Large deviation between measured value and actual value

   First, calibrate the zero point (close the valve after filling the medium). Check if the lining is worn or fouled, causing a change in the flow area. Confirm that the fluid conductivity meets the minimum requirement of the instrument (generally > 5 μS/cm).

Problem 4: Frequent empty pipe alarm

  Check if the measuring pipe is truly in a full pipe state. Adjust the empty pipe alarm threshold to a reasonable range. Clean or replace the contaminated electrodes. 

Question 5: Electrode Corrosion or Fouling

  Select electrode materials such as Hastelloy or tantalum based on the characteristics of the medium. Regularly disassemble and clean the electrodes. For easily fouling environments, use scraper or detachable electrodes.

Question 6: Bulging or Damage to the Lining

  Check if the medium temperature exceeds the temperature limit of the lining. Avoid operation under negative pressure. Choose lining materials such as PTFE or rubber that are suitable for the medium characteristics.

Question 7: Communication Failure

  Confirm that the communication protocol (such as HART, Profibus) settings are consistent with the master station. Check the cable length, shielding, and terminal resistance matching.

Question 8: Water Ingress Due to Insufficient Protection Grade

  Check if the sealing gasket of the meter housing is aged and tighten the cable interface. In humid environments, choose a protection grade of IP65 or above.

Question 9: Inaccurate Cumulative Flow

   if the time base and unit conversion settings in the flowmeter parameters are correct. Confirm that the pulse output settings match the receiving device.

Question 10: Interference from Variable Frequency

  Set up separate grounding for the frequency converter and the flowmeter. Use shielded cables and ground the shield layer at a single point. Install isolation transformers or filters at the power input end.

Regular maintenance is the key to the long-term stable operation of electromagnetic flowmeters. It is recommended to check the electrode condition, grounding resistance, and lining integrity every six months and perform a comprehensive calibration once a year. Establish a maintenance record, documenting each fault phenomenon and handling measures, which will provide valuable experience for quick diagnosis in the future.

Save this guide to make the maintenance of electromagnetic flowmeters systematic and effective, extending the service life of the instrument, ensuring accurate and reliable measurement data, and safeguarding your production process.


Follow me to learn more about the full life cycle services of flowmeters.